Measuring signals from resistance thermal meters, thermal couples, DC voltage, intensity and their conversion into unified current signals 0...5 mA, 0...20 mA, 4...20 mA.

  • Wide range of measured signals;
  • Galvanic separation;
  • Customer’s configuration option;
  • High conversion accuracy;
  • Explosion safety marking [Ехia]IIC or [Ехib]IIC;
  • Wall or DIN mounting options.

Manufactured in accordance with the technical conditions EI.107.00.000 TC

Использование Temperature

Normalizing converter measures the following signals:

  • From resistance thermal converters TSM, TSP with a nominal static characteristics 50М, 53М, 100М, 50П, 100П, Pt100 under GOST 6651-2009;
  • from thermal couples TKHA (K), TKHK (L), TZHK (J), TPP (S), TPR (В), TVR (A-1) under GOST R 8.585-2001;
  • D.C. intensity 0...5 mA, 0...20 mA, 4...20 mA;
  • D.C. voltages       0...75 mV; 0...100 mV;
  • resistances in the range 0…320 Ohm

and converts them into D.C. unified signals 0…5 mA, 0…20 mA, 4…20 mA with a linear or root-extracting dependence.

Example of ЭнИ-802M switching on

Example of ЭнИ-802M switching on

Analog signals converter configuration

Measuring converter configuration setting is conducted by the customer on-site or at the manufacturer’s plant by the customer’s order. Number of configuration resetting is unlimited.

Converter adjustment is performed:

  • with the help of a computer and configuring programme through a connector on the front plate and the adaptor ЭнИ-403 supplied by the order;
  • face plate buttons.

In the process of a normalizing converter setting one can change the following parameters:

  • primary converter type (input signal type);
  • input signal conversion range;
  • output signal range;
  • resistance thermal converter connection diagram (2-, 3-, 4-wire);
  • output signal dependence for thermal couples (linear from the temperature, linear from EMF);
  • input circuit break control (for thermal couples);
  • cold junction temperature compensation (for thermal couples).
Functional circuit of analog signal converter

Functional circuit of analog signal converter

1 — input signal converter unit;

2 — microcontroller;

3 — galvanic separation unit;

4 — shaper of output current and power supply unit (current and voltage stabilizer and voltage converter);

5 — IS and reverse polarity protection unit.

Key technical characteristics

ParameterValue
Output circuits are intended for the work with the loads, Ohm, for the signal 0...20, 4...20 mA with the account of the communication line resistance not more than 450
Output circuits (ЭнИ-802M-Ex) are intended for the work with the loads, kiloOhm, for the signal 4...5 mA with the account of the communication line resistance not more than 100
Output circuits are intended for the work with the loads, kiloOhm, for the signal 0...5 mA with the account of the communication line resistance not more than 1,5
Insulation strength between the input supply channel and output channels, V 1500
Structural design plastic body frame with a DIN or wall mounting option
Weight, kg not more than 0,2

Converter ЭнИ- 802М has no built-in power supply unit. Permissible range of the supply voltage change 18…27 V for the general industrial purpose version and 22…24 V for the explosion-proof one. Consumed power is not more than 0,6 W.

IS circuits

Measuring converters can be manufactured in the IS version by the order.

Input IS circuits in compliance with the requirements set in GOST R 30852.0-2002, GOST R 30852.10-2002 have the intrinsic safety level "ia – extra-explosion-proof" or "ib - explosion-proof" with the parameters for the explosion-proof electric equipment of the subgroups IIC. The limit parameters of external IS electric circuits shall not exceed the values given in the Table below.

Со, mkFLo, mHUо, WIо, mAPо, W
0,1 1,5 25,2 100 0,6

где:

Со — maximum capacity of an IS circuit;

Lо — maximum induction of an IS circuit;

Uo — maximum output voltage;

Io — maximum output current;

Ро — maximum output voltage.

A separating element between IS and spark-hazardous circuits is the IS barrier on duplicated stabilitrons, consecutively connected resistors and protectors having a galvanic connection with a grounding circuit and contained into a single integral structure in compliance with GOST R 30852.10-2002.

Communication line cable resistance shall not exceed 25 Om.

In compliance with the requirements stipulated in GOST R 30852.0-2002, GOST R 30852.10-2002 power supply units are installed outside explosion-hazardous areas.

Metrological characteristics at the operation with thermal couples and resistance thermal converters

Primary transducer typeOutput signal range, mAConversion range, °С

R100/R01),

α2)

Output signal dependenceγ3), %
50М-6 0…5 0…20 4…20 –50…+200

1,426

0,00426

linear - from the temperature ± 0,25
53М-6
100М-6
50М-8 –50…+200

1,428

0,00428

53М-8
100М-8
50П –50…+600

1,391

0,00391

100П
Pt100 –50…+600

1,385

0,00385

ТЖК (J) 4) –50…+1100 Linear from the temperature or linear from EMF ± 0,75)
ТХК (L) –50…+600
ТХА (К) –50…+1300
ТПП (S) 0…1700
ТПР (B) 300…1800
ТВР (A-1) 0…2500

1) R100 и R0 — — resistance values from NSC at 100 and 0 °С, correspondingly.

2) α — temperature coefficient of a resistance thermal converter.

3) Limit of permissible basic percentage error.

4) Thermal couple types under IEC 60584-3 are given in brackets.

5) With the account of the error of the cold junction temperature compensation.

Measuring converters contain an input signal non-linearity compensator as well as cold junction temperature compensation (for thermal couples). The "cold junction" compensation channel is included into the basic error.

Metrological characteristics at D.C. currents, resistance and voltage measurement

Input signal typeOutput signal range, mAConversion rangeLimit of permissible basic percentage error, %
voltage

0…5

0…20

4…20

0…75 мВ

0…100 мВ

±0,25
current

0…5 мА

0…20 мА; 4…20 мА

±0,25
resistance 0…320 Ом ±0,25

ЭнИ-802M external appearance

ЭнИ-802M external appearance

1 — terminal box to connect output power supply and grounding signals;
2 — LED "Norm" — on if there is power supply and the primary converter is connected;
3 — LED "Break" — flashes at the break in the primary converter circuit;
4 — buttons for the converter configuration;
5 — connector for the adaptor;
6 — terminal box to connect a primary converter;
7 — DIN-rail;
8 — warranty label.

Connecting ЭнИ-802М to a PC through the adaptor ЭнИ-403 via the interface RS-232

Connecting ЭнИ-802М to a PC through the adaptor ЭнИ-403 via the interface RS-232

1 — measuring converters ЭнИ- 802M;
2 — LED "Connection" is on when there is a connection adaptor-PC;
3 — adaptor ЭнИ-403;
4 — modem connection cable DB9F-DB9M (included in the adaptor contents of delivery);
5 — computer.

Connection diagram of a converter to the resistance thermal converter by means of a 4-wire circuit and output current signal 4…20 mA

Connection diagram of a converter to the resistance thermal converter by means of a 4-wire circuit and output current signal 4…20 mA

V1 — multimeterр;
R1 — load resistance;
Тс — resistance thermal converter.

Converter connection diagram to the thermal couple with output current signals 0...20 mA and 0....5 mA

Converter connection diagram to the thermal couple with output current signals 0...20 mA and 0....5 mA

V1 — multimeterр;
R1 — load resistance;
ТП — thermal couple.

 

Connection diagram of a resistance temperature converter by a three-wire circuit

Connection diagram of a resistance temperature converter by a three-wire circuit

Connection diagram of a resistance temperature converter by a three-wire circuit

Connection diagram of a resistance temperature converter by a three-wire circuit

Connection diagram at the D.C. voltage measurement

Connection diagram at the D.C. voltage measurement

Connection diagram at the D.C. measurement

Connection diagram at the D.C. measurement

 

ParameterValue
Ambient temperature, °С -10...+50
In terms of climatic effect resistance at operation corresponds to the version group, under GOST R 52931–2008 С3
In terms of mechanical impact resistance at operation corresponds to the version group, under GOST R 52931–2008 L3
Ingress protection level, under GOST 14254–96 IP20

Warranty liabilities

ParameterValue
Warranty operating life, months 36 months since the commissioning date but no more than 42 months since the date of manufacture

Contents of delivery

NameDesignationNumberNote
Measuring converters ЭнИ- 802M  ЭИ.136.00.000 1  
Data Sheet  ЭИ.107.00.000ПС 1  
Operation manual  ЭИ.136.00.000РЭ 1 at the supply it is allowed to supply 1 piece per 20 converters delivered to one address
Connection cable modem DB9F-DB9M 1 by order
Optical disc with software   1
Adaptor ЭнИ-403  ЭИ.144.00.000 1
DIN rail NS35\7,5 м by order

Designations at the order

ЭнИ-802МExia0...50°С50М-840...5360ГП
1 2 3 4 5 6 7 8

1. Наименование.

2. Explosion-protection availability and type designation:

  •  Exia — extra-explosion-proof;
  •  Exib — explosion-proof;
  •  no symbol — general industrial purpose.

3. Conversion range.

4. Primary converter type (do not specify in case of voltage, current and resistance measuring).

5. Thermal converters connection diagram:

  • 2 — 2-wire circuit;
  • 3 — 3-wire circuit;
  • 4 — 4-wire circuit.

6. Output signal range:

  • 0…5 — 0…5 mА;
  • 0…20 — 0…20 mА;
  • 4…20 — 4…20 mА;

7. Additional technological no-failure operating time up to 360 hours.

8. State calibration.